Corrected issue where the project download would fail

Bug Fixes

General

  • Corrected issue where the project download would fail from VC4 controllers. This would happen if the SSL setting was off on the touch screen and the VC4 controller was hardened to use HTTPS connections. Note is SSL if enabled on the touch screen it will always look for a HTTPS connection from the control system and not accept HTTP.
  • Corrected issue where the backup project would not come up after a failed project download from a VC4 controller. This issue was introduced in version 2.006.0046.
  • Corrected issue where the touch panel was not properly handling the authentication message for a NTLM Proxy.
  • Corrected issue for Microsoft Teams Panel where Device Type was showing as Null, this issue was in version 2.006.0046

Additional Notes:

  • Important Note: For firmware versions 2.004.0033 and higher, the Chrome Browser is no longer part of the firmware image and will be downloaded from Crestron’s auto update server, during the bootup sequence. Therefore, the touch screen will need to access the update server’s URL shown below: https://crestrondevicefiles.blob.core.windows.net/70- series/production/applications/manifest_x70_apps.json