New / improved features and fixed issues

Improvements

  • BG-T2758 Added Commissioning Mode feature binaries for the following devices
  • Miniserver (Version 13.03.01.15)
  • Miniserver Compact (Version 13.03.01.15)
  • Tree Extension (Version 13.03.01.24)
  • LED Spot RGBW Tree (Version 13.03.01.15)
  • LED Spot WW Tree (Version 13.03.01.15)
  • LED Ceiling Light RGBW Tree (Version 13.03.01.15)
  • LED Pendulum Slim Tree (Version 13.03.01.15)
  • LED Ceiling Spot RGBW Tree (Version 13.03.01.15)
  • LED Ceiling Spot WW Tree (Version 13.03.01.15)
  • We want to give the installer direct feedback and a better overview wether the tree connection is faulty or not.
  • Lighting devices will now visually provide information whether the tree connection between tree extension and device is ok or faulty, when they are not paired with the miniserver.
  • A “OK” connection is indicated by white light (with additional green led ring in case of RGBW-Spots, Pendulum, etc.), a faulty connection is indicated by either no light (WW-Devices) or a red light (RGBW Devices).
  • Config Performance Improvements
  • Faster startup (50% faster)
  • Faster document open/close (60% faster)
  • Faster object insert (80% faster)
  • Faster document tree update
  • Less idle CPU usage in opened project view
  • Faster edit
  • Faster save to Client/Gateway
  • General performance improvements
  • Faster save to Client/Gateway, Save is now done asynchronous in multiple threads
  • Faster Paste
  • Fast Select
  • A3D9-T993 SD format in background
  • A3D9-T993 Backup in background
  • Window can be closed/minimised
  • New function block Spot Price Optimizer
  • Activate a load at times where your energy price is cheapest
  • A3D9-T928 Energy Flow Monitor: Name & Icon of residual value
  • A3D9-T904 NFC Code Touch function block validity options for NFC tags and codes
  • A3D9-T905 Device Count for Modbus
  • A3D9-T853 Added additional authentication configuration for the user and an text input for the access controller
  • A3D9-T902 New NFC Authentication Types (Code or NFC, 2FA, NFC, Code)
  • A3D9-T895 Added scroll function for info pinner
  • A3D9-T886 Added comparison of inputs for status block
  • Comparing inputs by writing e.g. <v1> in the value field (similar to the Status-text field)
  • Comparing text inputs with numerical operators (&lt;, &lt;=, &gt;, &gt;=) is not supported
  • Conversion of Utility Meter to new block via context menu
  • A3D9-T870 Info banner when client project is open
  • A3D9-T575 Added excel sheet that lists power usage
  • A3D9-T109 Project Planning is resized to screen size, if screen size is smaller than the default planning tool size
  • A3D9-T266 AutoSave for project planning tool
  • A3D9-T574 Automatic connection of multiple selected equal inputs
  • Reset Miniserver to factory settings from context menu
  • Belimo auto-Addressing dialog
  • Audio Player: New input Custom sound for playing event files
  • A3D9-T906 New parameters, Vs for the Mixing Valve Controller and Ps for the Intelligent Temperature Controller (same as IRC valve stand still)
  • A3D9-T289 Tooltip when creating a new trust
  • A3D9-T585 Added web service for longitude, latitude and sea level
  • miniserver/dev/sps/setlocation?latitude=48&amp;longitude=14&amp;sealevel=572
  • miniserver/dev/sps/setlocation?longitude=14&amp;sealevel=572
  • miniserver/dev/sps/setlocation?latitude=48
  • Search of Miniservers
  • Possibility to enter IP address range for IP scan
  • A3D9-T841 Weather Data is requested as a zip file
  • Project Planning: Added new spots
  • LED Ceiling Spot RGBW Tree: 100503, 100504
  • LED Ceiling Spot WW PWM: 100505, 100506
  • BG-I20674 Sauna Controllers: Added new input ‘On’
  • A3D9-T925 New Systemmessage reporting device updates available with the possibility to start the updates directly.
  • A3D9-T1 Devices no longer update during pairing. Only during the desired AutoUpdate time (default 02:00) or manually via the device manager (context menu).
  • A3D9-T910 Editing icons in a multiple selection of function blocks is now possible (if the function block supports Icon editing)
  • A3D9-T648 Use same format for Loxone serial numbers in all places
  • New languages Vietnamese &amp; Bulgarian
  • BG-T2794 Music-Player: add custom TTS-language
  • Transfer of Manager role to another Miniserver
  • Transfer ownership of Users to another Miniserver
  • Error message when too many messages are sent
  • Communication improvements
  • Authentication NFC Code Touch: Added output for last authorised user, including Trust hostname if from another trust (without NFC ID)
  • BG-I21789 added online state object for HTTP VirtualIn objects
  • Modbus:
  • Adapted default polling cycle
  • Show register setting in red when nothing was entered
  • Valve Tree: improved status feedback on wrong cabling
  • Loxone Config 14.0 splash screen

Fixed

  • General
  • Updated used Frameworks &amp; Compilers
  • BG-I19288 Miniserver compact has wrong icon in multi edit dialog
  • BG-I19231 Project Planning: Wrong ‘Under Bed’ presence sensor added for new sleeping rooms
  • BG-I19314 Sauna Controller: Ready state not correctly using bench temperature and correction
  • BG-I19367 Comparison function block have problems with very small differences (0.001) resulting in invalid ‘equal’ result e.g. (1.001 &amp; 1.002)
  • RN1-I767 Energy Manager: Value range not shown in tooltips
  • RN1-I773 Energy Flow Monitor: Unconfigured control not shown in app
  • Energy Flow Monitor: Not a favourite per default
  • Audioserver system status message: Confirm does not work
  • Trust: User tokens not invalidated when changing password on another trust member
  • DMX Extension: DMX device search bugfix
  • BG-I19891 IRC V1: typo in description of parameters Ths + Tcs
  • BG-I18809 local hostname not resolved always correctly when multiple ip addresses were in the dns answer
  • temp files were not deleted after routed network device update
  • increased timeout for routed network device update
  • Improved Statistic analysis for Version 2 statistics
  • BG-I18809 local hostname not resolved always correctly when multiple ip addresses were in the dns answer
  • BG-I18987 DMX Extension Page Clamp description cut off
  • BG-I18997 Internal Airbase has no Device-Information option
  • BG-I18592 Climate Control Selection Dialog reverts setting in Room Controller
  • BG-I19041 Modbus RTU: automatically set stop-bits based on parity
  • BG-I19025 Music Server Zone: API-connector-line drawn with offset
  • BG-I18288 Gate: state change of Ic not taken into account for last driven direction
  • BG-I19160 Climate Controller limC cant be set higher than limH
  • BG-I18993 Starting Monitor in dialog not working
  • BG-I19159 Room/Category dialog favourite checkbox cant be unchecked
  • A3D9-T459 Remove confusing update message when loading from miniserver
  • BG-I19154 corrected UX of search button in Dali learning dialog during search is running
  • BG-I19277 Modbus Actors sent even if they are not used
  • BG-I18199 Sequence Control Dialog: new IF-formula causes incorrect indentations
  • BG-I18156 Sequence Control Dialog: “-” operator not spaced correctly
  • BG-I18910 Daytimer: output Mode renamed to “Om”, show liveview without digits
  • BG-I19213 Connector-names cut off if room/category is too long
  • Power Supply &amp; Backup: do not lock visu for common system messages
  • BG-I19333: Devicestatus: log file not shown when connected externally
  • BG-I17158 Sequence Controller: finished sequence shown as active
  • Miele@Home
  • States not updating
  • Energy consumption has no decimal places
  • Old installed files not deleted when installing Loxone Config over existing installation
  • BG-I19345 Invalid filter text
  • BG-I19495 Setting grid: border not correctly displayed
  • Monitor: Changing filter stops autoscroll
  • BG-I18025 API Connector Media Controller Double Click is not recognized by the API Input
  • BG-I17450 ITC AQl output calculation incorrect for cooling mode
  • BG-I19412 SMTP Mailer: invalid order of header-elements when adding attachments
  • BG-I6899 Analog Memory: edges caused by time-objects not handled by all connected controls
  • BG-I19514 Central Controls: lock via app does not lock all assigned controls
  • BG-I19524 Climate Controller: no automatic popup
  • BG-I19574 DeviceStatus: no channel-check for US and IL Channels
  • Switch: Activate remanence per default
  • Changelog dialog not properly sized
  • Converted Statistics file (e.g. Utility Meter) contains invalid timestamps due to errors in old files, causing wrong lifetime statistics
  • BG-I19272 Daylight savings: Client program reported as outdated
  • Modbus TCP: Some test commands not working, test commands not correctly displayed in monitor
  • Reworked Tree device search
  • Miniserver uses the list of devices which the Miniserver already has additionally to the active search
  • Miele@Home: Added user agent to API requests
  • BG-I19613 Message Boxes appear while converting energy monitor / utility meter
  • Miniserver does not respond to unicast search requests
  • Multi Edit dialog for IO cant be opened from program page
  • Control preset cant be multi edited
  • Port not set when replacing network device
  • BG-I20050 Add only one connection per object (Drag&amp;Drop)
  • BG-I19957 Project Planning: Multi Extension causes a second power supply &amp; backup
  • Update dialog fails when Miniserver changes its IP
  • BG-I19420 Device Status: Enocean devices displayed as offline
  • Enocean Actors displayed as dummy devices
  • BG-I19775 Virtual Output template: Answer property not saved
  • BG-I19680 Systemmessage: User can have visualisation limited
  • BG-I19695 Identify possible on 1-Wire device
  • BG-I19774 Saving template with @ in password
  • BG-I19769 API Actor not automatically connected to API output of block
  • BG-I19708 Documentation: Info Boxes not displayed correctly
  • BG-I20020 Ribbon: No separator between Link and Extension specific buttons
  • BG-I20127 Paste of devices not working after load from Miniserver
  • BG-I20118 Multiplicator: Light Group assignment gets lost
  • BG-I19917 Room assignment of devices get lost when adding project to gateway
  • BG-I19270 Custom icons not visible in Config since they are not coloured by the app and therefore need to be in light colours
  • BG-I20048 Miniserver Configuration: Internal address is set to ip instead of hostname
  • BG-I20129 Statistics: Every Change (Expert) does not write an entry on day change
  • Miniserver unable to load project due to invalid object count
  • BG-I19702 Statistic files containing entries from other months
  • BG-I20053 Adapted power connector letters
  • BG-I19686 Program always shown as not identical when there is a duplicate KNX address
  • Endless loop when entering specific IP address scan range
  • BG-I20112 Invalid permissions when user is created via app
  • BG-I20309 Lightcontroller: remove from favourites changes order in config
  • BG-I20291 Power supply &amp; backup dialog: prevent pasting of control characters
  • BG-I20232 Operating Time: adapted default name and object type name
  • BG-I20140 Miniserver Compact: new Tree Device-Bubble shown on wrong extension
  • Newly added user does not have any permissions to controls on a client
  • Power Supply &amp; Backup: Systemmessage does not contain room of device
  • Audio Identify of Compact not working when Compact is a Client Miniserver
  • Belimo Monitor remains active after Loxone Config disconnect
  • Improved Config connection reliability
  • Improved performance of table view with large data
  • Improved performance of System status
  • Spot Price Optimizer uses too many time slots
  • Schedule: Mode not updating in visualisation
  • BG-I20384 Project view does not close after Miniserver search
  • BG-I20017 No Device-Command context menu for Tree to Air bridge
  • BG-I20014 Automatic rule: severity-levels not identical with custom system message
  • BG-I20013 Device Status: remove unsupported commands from 1-Wire-Extension
  • BG-I20083 DMX Device: invalid next dmx channel when using 1-actor-types
  • BG-I18129 HTTP Virtual Out only sent POST request when body data was provided
  • BG-I20023 updated address conflict message in Dali learn dialog
  • BG-I20421 NFC LearnDialog: Learning could be started even on unavailable devices
  • BG-I19848 fixed jumping scrollbar in tech doc viewer when there are multiple gifs present
  • Starting Miniserver search from project view while already a project is opened connects in the opened project
  • Audio Central: Client restart causes resend of tts command to Audioserver
  • BG-I18428 Tree2Air-Bridge: sleeping Touch&amp;Grill goes offline when saving into Miniserver
  • BG-I18212 Touch&amp;Grill: switching room not possible after inserting controls in a certain order
  • Touch&amp;Grill: Wrong room assigned after dragging on page
  • BG-I15908 fixed inconsistency on Lighting Controller Circuit Naming
  • BG-I17217 Caller Service Add additional spam error message at too many calls
  • BG-I20744 Fixed tracker minimal time interval. Values below 21ms are considered as 0.
  • Fixed System message indicates that a device is updating even though the device is finished updating
  • BG-I20784 Fixed icon multi edit over shared properties window
  • BG-I17710 Fixed shading central restarts by itself after stopping via Pc
  • BG-I19537 / BG-I17772 Scene on a client can not be triggered by an object connection
  • BG-I20841 KNX Sensors not updated on page when showing/hiding error output
  • BG-I20836 Output on another Miniserver cant be switched anymore after it was switch via LiveView
  • A07R-I309 Documentation: Range not displayed for some IOs
  • 1-Wire Monitor: Entries have no level (data, error), making it difficult to filter
  • LiveView/Simulation: Removed value adjust via mouse drag
  • This caused unwanted changes of values in installations when trying to move a reference
  • Simplified printing project
  • Only one print action
  • Automatically select current selected page in print dialog
  • LiveView: Display correction only if there is enough space
  • Monitors not working when ‘Position windows freely’ mode is active
  • BG-I20874 Integrated blind shown as not configured
  • BG-I20872 Connection to API output not created properly when done via connection window
  • Tree search shows results without serial
  • BG-I20723 AutoConfig: Tunable White shown as RGBW
  • Burglar Alarm: Opening configuration dialog is necessary to update names of used sensors
  • BG-I20702 Added hostname including domain to LoxAPP3.json (if the Miniserver is on DHCP)
  • BG-I20708 LiveView/Simulation: Nothing displayed on inputs of status block
  • Fire and Water Alarm: Use more descriptive names IOs which cause an alarm
  • Same handling as Burglar Alarm
  • BG-I20785 Confirmed error messages are also shown in document trees
  • Miniserver serial cant be entered without colons
  • Connect dialog does not set external address when connecting to Miniserver without internal address
  • BG-I19126 fixed crash and address conflict resolution in Dali learning dialog
  • BG-I20025 fixed incorrect address check in Dali learning dialog
  • BG-I20722 Deactivated update available message for devices which are offline or have the version 0.0.0.0
  • BG-I19530 Wallbox Gen. 1: Profile change during charging caused a jump in energy consumption for the newly selected profile
  • BG-I19669 Fixed copying of a value from the property window, when it’s not pinned
  • Tree2Air-Bridge: Device-Webservice &amp; Device-Info not executed
  • BG-I12602 Geiger Solidline: API-Output is created with conversion when command-output is used
  • BG-I20715 System Status: view jumps to top after confirming message
  • BG-I20691 Remote Air does not extend the presence
  • BG-I20546 Air learning help link not working
  • BG-I20447 Schedule: Inverted output invalid when starting manual timer
  • BG-I20729 Statistics: Removed handling to only write values to the statistic file if they have changed
  • Now values are always written in the defined interval
  • BG-I20701 Power Supply &amp; Backup not displayed in energy flow monitor when user has no rights for it
  • BG-I20618 IR Module search not working
  • BG-I20719 Generic View Filtering: Improved search/filter when texts include special characters (:.;) e.g. for serial numbers which now contain a colon
  • BG-I20732 PicoC text output edge not reset
  • BG-I20565 Search does not give any results when starting it after opening project view
  • BG-I19639 Miele devices displayed offline even if they are online
  • BG-I20746 Burglar Alarm: Tracker entries and text output does not contain enough information to distinguish sensors
  • added device name or installation place, depending on if the device was renamed
  • Remote Connect: Connection establishment did timeout in some cases when ipv4 and ipv6 nameservers are available
  • BG-I20457 ensuring that text in monitors is always readable depending on background colour
  • BG-I20406 virtual command edit dialog did not request full url parameters
  • BG-I19681 ensure NFC learning command is also sent to battery driven Air devices
  • BG-I20030 only enable resolve conflict button in dali learning dialog when needed
  • BG-I20021 show error message when trying to add/assign dali device with already assigned address
  • Presence links are shown as memory object in the periphery tree
  • Miniserver Compact: too many audioserver-tasks started
  • BG-I20132 Device Learning: Automatic blinds offline after replace via app
  • Periphery tree filter: ‘Do not use’ shows items without room/category
  • Caption bar changes when connection gets lost in another document
  • BG-I19420 EnOcean devices displayed offline in device status
  • BG-I20545 Mouse over shows hidden tree extension on Miniserver compact
  • BG-I20555 Removed error message when using custom inputs for UDP port 7090
  • BG-I20408 Setting Edit dialog shows non working links
  • BG-I20532 Project analysis: Shows duplicate address even though when port is different
  • Allow cloud dns connect with Serialnumber including colons
  • BG-I17800 Radio Buttons: Allow web service command ‘next’ &amp; ‘prev’
  • Too many old program files get deleted when saving to Miniserver
  • Activate watchdog for IO Task
  • BG-I20891 Wallbox g1: Charging Power is always 1kw
  • BG-I20911 Miniserver search when filter is active does not show items
  • BG-I20902 Manage SD card dialog: Text overlaps button
  • BG-I20910 EFM: Meters get lost when adding project to gateway
  • Config/Miniserver memory leaks
  • Dali: removed deprecated settings (RGBWAF channel assignment)
  • BG-I15822 Dali: Fade Rate gets invalid value after replace device
  • BG-I19373 NFC Code Touch: no app update if code expires shortly after creation
  • BG-I20909 Monitor: Keycode information not shown if “force preselection” is activated
  • BG-T2795 Miniserver-Replace: audioserver not paired with new device
  • BG-I20906 + BG-I20932: DMX Extension: Invalid values sent to actors
  • Actors not switching
  • BG-I21006 Search/Filter for Air serial numbers in Config
  • BG-I21051 Nano DI Tree: Not all information displayed on cover page
  • BG-I21003 Touch Surface Dialog: Max. material thickness not validated
  • BG-I21024 Known Issue dialog not opening on click
  • BG-I21039 API Command text in table cut off
  • BG-I21020 Touch Pure Flex: Initial value not set in Menu command
  • BG-I21052 Copy of KNX IO not possible even if Cut is possible
  • BG-I18945 Touch Pure Flex not selectable as output in alarm objects
  • Update: Miniserver Gen.1 Update not working due to too short timeouts
  • BG-I20949 EFM: Self Consumption output zero
  • BG-I20936 Miniserver replace: Connect to gateway not working without IP &amp; Config crash when there is no Audioserver
  • Reworked device updates available system message
  • Tree Devices: Fixed CAN was not initialised properly during startup if 24 V was connected to CAN
  • BG-T2825 TreeBase: Fixed init sequence which lead to a non functional Tree2Air bridge
  • BG-I21069 Touch &amp; Grill causing Black screen in App
  • BG-I20029 hide already learned Dali devices in learning dialog, except “new installation” option is checked
  • BG-I20745 name of learning Enocean device wasn’t taken over correctly
  • BG-I20738 added serial number column in Enocean learning dialog devices list
  • BG-I20737 corrected highlighting of new learn data in Enocean learning dialog
  • BG-I20789 fixed authentication url with email address as user in VIN command learning dialog
  • BG-I21394 fixed incorrect highlighting in some special cases in VIN command learning dialog
  • BG-I21009 Api Command on status block not working
  • Energy Manager Gen.2: Lower prioritised analog load does not get turned off when there is enough power for higher prioritised analog load
  • Nano DI Tree: Text on cover page too long
  • Include Alpha Web Interface
  • Weatherstation: Removed unused hidden inputs
  • BG-I21146 Miniserver replace: Miniserver not identifying in search
  • BG-I21147 Miniserver replace: Continue with enter on credential page
  • BG-I16359 Chart View: X Label to the left is cut off (presence configuration dialog)
  • BG-I19470 New statistics write value 0 to statistics on reboot
  • BG-I19122 Poolcontroller: Automatic Designer texts not available in the app
  • BG-I21407 Connection flag creation: Page window is opened outside of view
  • BG-I21396 Reference shows more information button
  • BG-I21283 User created operating modes get high IDs
  • BG-I18438 Presence Sensor Overrun Time P reset after power cycle incorrect
  • BG-I20981 Tree search on a intercom on a client not working when intercom block is not inserted
  • BG-I21162 Part List: Power supply &amp; backup missing
  • BG-I21234 Adapted air signal strength qualification
  • BG-I21199 Intercom Gen.1: iButton learning not possible
  • BG-I21338 Touch Pure Flex: Command on central function block (e.g. central shading) is not sent to all objects (only sent to the controls last selected in the app)
  • Emergency Button can’t be triggered via API command
  • Touch Pure Flex: Value selection in config has a shorter timeout than the device
  • Config locks up when loading from Miniserver
  • Plugin dummy device state not updated when changing api user setting
  • BG-I21008: DMX device DMX actuator RGBW can’t set type of actuator
  • BG-I21090: Project Analysis: show duplicate Address/Channel settings for Belimo + DMX
  • BG-I17846 IR Extension/Module Learning not working
  • BG-I21909 Tree filter dropdowns empty in new project
  • BG-I20562 better error message in case start command failed in NFC learning dialog
  • BG-I21100 corrected DMX default name assignment when inserting device via DMX learning dialog
  • BG-I19714 default name was not correctly propagated when left empty in 1-Wire learning dialog
  • BG-I21761 popup in table views caused close when clicking in empty area
  • BG-I21763 first opening of detached monitor window showed all monitors
  • BG-I21802 search kicked message dialog shown for air and tree even though search was not running
  • BG-I21453 Device Status: invalid online state for Sonnen-Battery
  • BG-I21756 System Message for failed certificate: add information about reachability of internet and cloud-server
  • BG-I21809 Wallbox: relative metering doesn’t work
  • Dali Monitor:
  • Data flow is slow
  • Show errors in colour
  • Fixed wrong direction
  • Dali devices not sorted by name in document tree
  • BG-I21165 Monitor: Cancelling loading still empties monitor
  • Dali: Readded off to Power-On options
  • BG-I17585 Parameter cant be edited anymore after being set via API command
  • BG-I21726 Tree diagnosis cant send data when monitor is running at the same time in a big installation
  • BG-I21686 Invalid search answer for app learning when searching in a gateway
  • Touch Pure Flex: Arrow commands executed twice when in pulse mode
  • Extension serial cant be entered with colons
  • BG-I17713 Switch of mode via LiveView not working when calendar is active
  • BG-I21486 “Don’t show again” checkboxes are not remembered after installing new version
  • BG-I21599 Extension update starts without being started
  • BG-I21600 Remove sensitivity settings from inputs which currently don’t support it
  • BG-I19005 No device type for Miniserver displayed
  • BG-I21706 Control Linking dialog: Memory leak and invalid display
  • BG-I21693 Shorter validity for Loxone Config tokens
  • BG-I21516 Object stays partially selected when unselecting in tree
  • BG-I21390 LiveView: Yellow line not correctly displayed when value is zero
  • API Command dialog: Wrong command preselected
  • BG-I21441 SubControls contain “hasControlNotes” flag
  • BG-I21550 No Info on control when used in system schematic
  • BG-I21548 Unstable config connection when searching for tree devices on a gateway
  • Certificate systemmessage: removed help link
  • BG-I21515 Page scrolling continues after page change
  • BG-I21532 Property window: Scroll jumps when window is updated
  • BG-I21536 Wrong selection after deleting device from device tree
  • BG-I21478 Miniserver not correctly rebooting after update
  • No warning when using a hostname for a client as internal address
  • Reduced debug Monitor outputs
  • BG-I21592 Plugins: Online state is not per default monitored
  • BG-I21542 MENU Api Command: Added more info about start value
  • “If the current value does not represent an option, the first option will be used as the start value.”
  • Improved speed of insert of multiple references
  • BG-I21072: App access code on NFC Code Touch cannot be deactivated in the app
  • Presence Tree: invalid default parameter after creating
  • BG-I21580 Media Controller: always execute “change to mode”
  • BG-I20751 Media Controller: reset via double-click does not finish command list
  • BG-I20988 Remove unused sensibility settings for Modbus-Sensors
  • BG-I16157 Usermanagement: Automaticdesigner not visible after editing groups
  • IO Data serialised twice to xml for air devices
  • BG-I21399 Dimmer: Value Selection on touch pure flex does not start with actual value
  • BG-I21430 Page scroll jumps after editing name of page
  • BG-I21450 Identify from tree not stopped when clicking in empty area of tree
  • BG-I21070 Proxy not properly closed when using ssl
  • BG-I21467 Statistic dialog cant be closed with escape after deleting a statistic
  • Emergency Alarm shown as unconfigured when only Alarm input is used
  • BG-I21082 Meter reset not correct, when reseting multiple times
  • Project cant be opened anymore after learning devices
  • BG-I21209 Tree device learning: Identification of devices in Config not working
  • Generic Table: Delete empties wrong cell when table is filtered or sorted
  • Miniserver compact: duplicate audioserver after re-adding gateway client to document
  • Updated installer
  • BG-I21487 Presence Control: Statistics Record Every Second
  • BG-I21966 DMX actors change room assignment to “do not use”
  • BG-I21808 fixed incorrect request when invoking test command on HTTP VirtualIn
  • BG-I21800 Integer block result was incorrect for negative values in some cases
  • Invalid dns domain name breaks LoxApp
  • BG-I21949 Output to Output connection via reference not completely deleted when deleting reference
  • BG-I22038 Config cant be closed after opening project planning file
  • BG-I21905 Config problems when drag and dropping incompatible files onto Loxone Config
  • Document is modified when double clicking objects
  • BG-I22221 ‘Switch (On/Off)’ has option for statistics
  • BG-I21811 Test command button disappears from ribbon and does not reappear
  • BG-I22143 Energy Manager: Memory changes type to analog when connected to output
  • BG-I22227 System Schematic flag remains when copying control from another project
  • BG-I22034 Dali Config improvements (Missing setting updates, clearer info when device has no address, naming after learning,…)
  • BG-I21697 Fire and Water Alarm Output N is not set to 0 when Off input is used
  • BG-I21689 Alarm Chain Output gets triggered once too many
  • BG-I21607 Handling a group of API commands separated by &amp;
  • BG-I21586 Fixed object type name for NFC Key-Tags
  • BG-I22183 Intelligent Room Controller: Presets for Roomtype not applied
  • BG-I21110 Custom System Message not shown for allowed Users which have no access to triggering control
  • BG-I18777 Apostrophe in Miniserver name breaks admin interface
  • BG-I22148 Template button in ribbon has no action
  • BG-I22050 Document tree collapses on undo
  • BG-I21747 Invalid connection when connecting multiple memory inputs with different types
  • BG-I22142 Merged object cant be edited in multi edit window
  • BG-I22018 Opening system schematic set document to modified
  • BG-I21923 Valve error system messages not shown anymore when device goes temporarily offline
  • BG-I22001 Miniserver search: Added miniserver configure button
  • BG-I22033 Room/Category dropdown not updated when loading from Miniserver
  • BG-I22051 Miniserver mDNS response invalid when many extensions are connected
  • IR Meter Reader Air (M-Bus): Before each readout, the firmware now sends a “SndNke” to always get the same response.
  • BG-I22068 Media Control Dialog: Escape does not close window
  • BG-I21465 Roof Window Shading: Output Op is switched on sequentially
  • BG-I22160 Modbus: Digital Actor Write Single register sends 0xFF00 instead of 1/0
  • Duplicated systemmessage for virtual HTTP Input
  • Unable to set ipv6 address as external address
  • BG-I21471 KNX Extension on wrong parent when converting Gen.1 to Gen.2 Miniserver
  • BG-I21491 Formula block: Division by zero in unused If result also results in an error (e.g. “IF(I1&gt;0;10/I1;10)”)
  • BG-I21719 App Learning: Search not stopped in app when search on another client is started
  • BG-I21721 Device Information of Miniserver shows wrong DNS
  • BG-I21745 Edit dialog not opening anymore after inserting control (e.g. burglar alarm)
  • BG-I21752 Receive timeout of analog input not directly reported
  • BG-I21777 Tooltip does not disappear
  • BG-I22070 Trust User: Token get deleted after update from trust owner
  • BG-I21625 Document Tree: Invalid tree root item
  • BG-I21790 Forward slash not allowed in block names
  • New icon for extension search
  • BG-T2934 Reduced delay in device proxy
  • BG-I20111 NFC: Access denied in App with authentication type “NFC (only)”
  • Schedule modes are invalid after update
  • LoxAPP not generated for standalone Miniserver when saving to Miniserver
  • No Page displayed after deleting all pages
  • BG-I22245 Mode: Switch in Simulation not working
  • BG-I22297 Air Channel does not revert to correct original channel when frequency change, which was started via context menu, is aborted
  • BG-I22351 Config shows program not identical
  • BG-I20689 Intercom: Bell input is available when intercom originates from another trust member
  • Network device does not display any serial number when address is not entered
  • BG-I19874 System Message unclear when Tree left and Tree right are connected
  • BG-I21412 Tree Shortcut systemmessage does not disappear
  • BG-I22219 AI Extension: Inputs are sorted by name
  • BG-I22253 Selection of multiple controls not working when there is a connection reference
  • BG-I22294 Room/Category may overlap for controls with only 1 visible input or output
  • BG-I14516 Steak Thermo: show “no sensor connected” in monitor and liveview
  • BG-I22030 API commands work even when Disable input of function block is active
  • BG-I22078 &amp; BG-I22078 Touch Flex: Updating configuration always completely resets button configuration (selected controls, show state,..)
  • BG-I22025 Runtime counter: Output not updating when unit parameter is changed
  • BG-I21810 Multiplicator: Users are shown as unsecure even when password was changed
  • BG-I21905 Config problems when drag and dropping incompatible files onto Loxone Config
  • Document is modified when double clicking objects
  • BG-I22221 ‘Switch (On/Off)’ has option for statistics
  • BG-I21811 Test command button disappears from ribbon and does not reappear
  • BG-I22227 System Schematic flag remains when copying control from another project
  • BG-I22034 Dali Config improvements (Missing setting updates, clearer info when device has no address, naming after learning,…)
  • BG-I22494 Project Overview: Miniserver type not updated when project is saved
  • Initial line origin when creating connection reference
  • BG-I21190 Touch Pure Flex Air: Does not send humidity anymore
  • BG-I21693 Shorter config token age
  • BG-I22128 Monitor can’t be stopped from within the Monitor dialog
  • BG-I22225 API commands: Value selection start value not taken over from selection switch
  • BG-I22311 Additional info text when creating trust key
  • BG-I20736 certain monitor types were stopped when starting learning dialog
  • BG-I22466 Intercommunication: Password gets corrupted when copying intercommunication object
  • Control references are not restored when cutting and pasting control
  • BG-I22530 Miniserver LED still reports error after caller systemmessage source gets deleted
  • Update dialog automatically put to background during update
  • BG-I21834 Sequence Controller Dialog: goto-commands update invalid when lines are wrapped
  • BG-I19373 NFC Code Touch: Missing app update if code expires
  • BG-I18796 NFC Code Touch Air: not possible to learn NFC tags via app when battery powered
  • BG-I21130 NFC Code Touch: Locked device also locks app user
  • BG-I21579 Expert Mode: not possible to activate statistics
  • Wallbox Air/Tree: product variants not visible in quicksearch
  • QU1-I208 Miniserver conversion: Settings of moved IO’s get lost
  • Program shows not identical after update
  • BG-I22325 Formula: Automatically remove line breaks
  • BG-I22350 Miniserver configuration: Dialog closed when pressing ENTER even when a textfield has the focus
  • BG-I22356 Opened dialog positioned to low so its behind taskbar
  • BG-I22315 Multi Connect with physical input and memory input: Hidden error output gets connection instead of input
  • Trust: Usercaption created on unnecessarily
  • BG-I22030 Disable does not disable API commands on all controls
  • BG-I22247 Room/Category dropdown on program page goes out of application
  • A07R-I328 Project documentation has missing settings
  • Further validate hostname on Miniserver Gen.2 and compact
  • Smaller edit and drawing issues
  • Miniserver usage not updated after delete/undo
  • Pages not correct after undo
  • Auto-Update on Miniserver Gen.1 not working due to high memory usage
  • Update is now downloaded directly to file when there is not enough memory available
  • New binaries (13.03.03.22) for Belimo Air/Tree (Fixing/Full support search by Serial Number)
  • BG-I22304 Air Base set to ‘Auto’ always does an auto learn of devices
  • Now it’s only done when there is a dummy device
  • BG-I22606 Format dialog: Broken selection when selecting Miniserver Compact backup
  • Assertion when closing document
  • Error message during connection establish
  • Miniserver update available message not shown
  • WA1-T298 WallboxTree is not working on internal Tree branch of Miniserver Compact

Devices &amp; Extensions

  • new Roomsensor Tree binary: activated CO2 autocalibration
  • new Valve Tree binary: changes to reference drive and position drive to 0%
  • IR Meter Reader Air: Reading out Elster AS1440 could result in frequently occuring system messages
  • new binary for Valve Actuator Tree: improved valve detection and force applied to valve
  • Multi Extension Air: Stability improvements of the digital inputs
  • Miniserver reboot loop after configuring Miniserver which contains an internorm blind
  • LED Ceiling Light RGBW Tree: Removed blink states of backwards LED on
  • added new binary for NFC Code Touch Air:
  • learn mode improvements
  • BG-I20383 NFC Code Touch: Code entry timeout loses preselection
  • BG-I19180 NFC Code Touch Air: Sleep mode doesn’t cancel held buttons
  • added new binary for Touch Pure Flex Air and Tree
  • BG-I20726 Touch Pure Flex Air VALUESELECT not working
  • Timekeeping improvements
  • Valve tree
  • added reference drive after firmware update
  • fixed valve stuck messages
  • Increased force to fix “valve stuck” messages
  • Improved internal error handling
  • BG-T1593: Weatherstation Air V2 added new binary FW-Version 12040309, fixed power on reset
  • BG-T1594: PacketSafe Air added new binary FW-Version 12040309, fixed power on reset
  • new binary for touch air: fixed BG-I21230: Touch Air: Touch not working in/after learn mode
  • new binary for room sensor air (HW 2): fixed device not sending values in 24V operation
  • New binaries (13.02.12.21) for Belimo Air/Tree (Fixes and de-address unknown)
  • Nano2Relay Tree (HW version 2): fixed devices going offline sporadically

Lighting

  • BG-I12390 Lightgroups go off during restart if actor is not on same miniserver
  • BG-I18405 T5 stuck in light controllers
  • BG-I19185 TW Smart actor: invalid On/Off state in LiveView
  • BG-I19751 Light Controller: moods still mixed after saving new mood
  • BG-I19705 Central light: with Off the selection is not observed
  • BG-I18909 Lightcontroller: Moods with stored sequences cannot be triggered when changing output type
  • I17292 Brightness-Change in Master-Color not applied for daylight-control
  • BG-I19472 Unable to dim Smart TW actor
  • RN1-I661 Daylight-states not updated for non-smart-actors
  • BG-I17633 Actor sends invalid values after adding to light group
  • BG-I19472 On/Off state incorrect when solely using TW-actors
  • BG-I22074 Dialog: operating modes not sorted alphabetically
  • BG-I21869 Light-Actors cannot be deleted after light group is removed
  • BG-I21444 Activating daylight does not change active mood

Energy

  • BG-I19601 EFM: Name of node gets lost in client gateway systems
  • BG-I19103 Utility Meter add value on miniserver start
  • Energy Flow Monitor: Meter on Client does not send values to EFM
  • RN1-I961 Energy Manager: Runtime per day and Minimum runtime wrong unit in the app
  • BG-I19010 Energy Flow Monitor: Program not modified when changing setting in dialog
  • BG-I19217 Energy Manager: Load which uses more power than provided not handled correctly
  • Meters of Power Supply &amp; Backup on a Client break the Energy Flow Monitor
  • BG-I20128 Energy Manager: Reordering breaks runtime variables
  • BG-I19719 Meter without dedicated Meter Reading does not apply offset
  • BG-I20090 EFM: Statistic of used Meter is disabled
  • Energy Manager: Analog load is not maxed out when its not drawing any power, therefore no additional loads get activated
  • BG-I19635 Power Supply &amp; Backup: Does Not write statistics on Client
  • BG-I21569 Energy Monitor conversion: Connection loss breaks conversion
  • Energy Flow Monitor: Does not show info of how many objects are assigned
  • BG-I19635 Power Supply &amp; Backup: Does Not write statistics on Client
  • BG-I21514 Energymanager: Overlapping Output Texts
  • Energy Manager: Output regulation not the same anymore as before resulting in activation of inactive loads with maximum (e.g. e-car when getting plugged in)
  • Energy Manager: Active load which does not use any power, gets deactivated as soon as another load uses power and power available for managing therefore goes to zero
  • Spot Price Optimizer: Shown in visualisation despite not having one
  • BG-I21797 Power Supply Control: invalid output RST in documentation
  • BG-I19552 Energy Flow Monitor does not use description of function blocks
  • BG-I22060 Pulse Meters: First energy not added to day/month/year
  • BG-I21921 Bidirectional Meters: Automatic connect of production/delivery meter reading inputs not correct
  • BG-I21921 Bidirectional Meters: Automatic connect of production/delivery meter reading inputs not correct
  • BG-I22143 Energy Manager: Memory changes type to analog when connected to output
  • BG-I22287 Energy Manager: Minimum runtime of load is ignored when managing grid power with an analog load
  • BG-I22345 Energy Monitor: Import total output only visible after conversion
  • BG-I22373 Energy Manager: Used power of load ignored when not activated by energy manager
  • Energy Flow Monitor: Residual icon &amp; name can be edited even when not enabled
  • BG-I21974 Wallbox: start/pause via app not possible when inverted input with additional logic is used
  • Wallbox: charging status not updated in app
  • Wallbox: Charge-session not ended when disconnected during load-shedding / limitation below min-value

Climate

  • BG-I20032 Intelligent Temperature Controller: override-inputs always shown english in visu
  • BG-I20281 Intelligent Temperature Controller: set default colour to type “climate”
  • BG-I20334 Climate Controller: untranslated text in app
  • BG-I20468 Intelligent Temperature control: outputs not activated after reboot of gateway client
  • BG-I18463 + BG-I20079 Intelligent Roomcontroller: fixed setpoint in fahrenheit converted incorrectly
  • BG-I17499 Intelligent Roomcontroller: window contact not considered in changes of outdoor-temperature
  • BG-I9282 Intelligent Roomcontroller: prepare heating ignored after first day of operating time with duration &gt; 1 day
  • BG-I20451 Intelligent Temperature Control: state not updated after miniserver-reboot
  • BG-I18991 Intelligent Room-Controller: output value changed multiple times during shutdown of climate controller
  • BG-I20857: Climate Controller Dialog: Checkboxes not remaining
  • BG-I20793 Climate Controller: If setting ϑlimC and ϑlimH via own logic it still can be changed in the app
  • BG-I21225 IRC: Mode 3 does not take over the target temperature
  • BG-I21259 IRC: Liveview when using PWM Outputs not updated
  • BG-I20777 IRC: Reset to Default doesn’t reset selected mode
  • BG-I20377 IRC: selected mode via app persists after connecting mode-input
  • BG-I20933 IRC: Error-Message for big difference comes immediately when manually starting comfort mode
  • BG-I21339 Climate Controller: missing remanence
  • BG-I22076 IRC Setting limits can be overruled with multi edit

Shading

  • Automatic Shading Central: Change direction while moving.
  • Automatic Jalousie: Invalid End Position for Full-Up-Movement in simulation
  • BG-I21637 Central Shade: direction change via T5 incorrect
  • BG-I21637 Central Shade: direction change via T5 incorrect
  • Automatic Jalousie: Invalid End Position for Full-Up-Movement in simulation
  • BG-I21606 Automatic Jalousie: Shading moves completely when two commands are sent in succession
  • BG-I21755 Automatic Shading Integrated: connecting a dummy motor causes infinite recalculation loop
  • BG-I21606 Automatic Jalousie: Shading moves completely when two commands are sent in succession
  • BG-I22402 Automatic Jalousie: allow pulse up/down commands via app
  • BG-I21926 Automatic jalousie: invalid behaviour in simulation when using Nano2Relay tree

Belimo

  • BG-I19474 Belimo learning: multiple identify commands when adding device
  • Device found via Address-Button after manual creation
  • BG-I20494 Belimo: Inherit room of device to IO’s, add devices to devicestatus
  • BG-I21157: Belimo Add Device Dialog learned in devices not shown
  • BG-I20985: Belimo: fixed naming of child-IO’s
  • BG-I21095: Belimo manual addressing: charset problem on result-message
  • BG2-T245: various bug fixes for Belimo learning
  • BG-I21703 Belimo: cut and paste of Sensor sets to “not configured”
  • BG-I21762 Belimo Monitor: some Data contains “:” others not
  • Belimo Addressing: invalid device type
  • Belimo Addressing: device created on wrong Belimo Air/Tree
  • BG-I22282 Show deaddress-warning before deleting Belimo device
  • BG-I21472 Belimo Devices: No “Monitor Online Status” Option
  • Belimo: devices without serial not shown as dummy device
  • BG-I19419 Belimo: Systemmessage cannot be confirmed
  • BG2-T261 Improved Belimo Addressing
  • BG2-T259 Belimo: Sensor/Actor limitation is calculated on actual usage
  • BG2-T258 Belimo: show Addressing-Error in search-dialog
  • BG-I19419 Belimo: Systemmessage cannot be confirmed
  • Belimo: Malfunction/Maintenance handling

Client-Gateway

  • BG-I20177 RS232/RS485 Monitor on Client/Gateway not starting
  • Adding client to gateway: Room/Category of light group get lost
  • Gateway/Client: Reduced memory usage during update
  • Miniserver Compacts in a Gateway show an error in project analysis
  • Sort Client Miniservers by Name and then by switchboard
  • Device Status: Offline client always shown Online and with wrong Miniserver type
  • Gateway file distribution is interrupted by trust updates
  • Gateway/Client Miniservers are sorted differently in program tree and pages than in periphery tree
  • Gateway shows outdated project system message
  • BG-I21483 Gateway: Update/project not transferred to slave due to failed discovery
  • Gateway: Client offline message does not disappear
  • BG-I20934 Gateway/Client: Statistic not working for objects on a client when it previously was on the gateway
  • BG-I21443 Client/Gateway: Audioserver connection on a Client not working after reboot (client not authorised)
  • BG-I21198 Gateway/Client: Object communication commands get lost in big installations (e.g. All On of more than 128 light controllers via central light)
  • BG-I18466 DMX Monitor not working in Client/Gateway

Trust

  • Trust: User gets deleted from all members directly after it was removed from the source
  • To prevent accidental delete the user is now disabled for a 1 day and deleted afterwards
  • Trust IO cant be deleted from context menu
  • BG-I21014 Trust: Usergroup deletion not handled correctly
  • BG-I21479 Trust Member Offline Message does not disappear when nothing is subscribed anymore
  • BG-I20887 Trust join fails when both Miniserver have the same local address
  • BG-I21479 Trust Member Offline Message does not disappear when nothing is subscribed anymore
  • Trust transferred nfc credentials not saved
  • Trust has missing user group caption

Multiplicator

  • BG-I20962 Miniserver status not updated when opening dialog
  • BG-I20791 No info which Miniserver is opened
  • BG-I22037 Configurable controls (e.g. Window Monitor) always set to modified after cancelling control selection dialog
  • BG-I21827 Changes get lost when directly updating a Miniserver
  • BG-I21827 Error handling when transfer of files to Miniserver fails
  • Save backup of programChanges.xml in backup path

Auto Configuration

  • BG-I21298 Auto Configuration: Added Todo to configure the volume thresholds of presence sensors
  • BG-I21296 Auto Configuration: Create a presence detection control in thoroughfares when there is audio (Audio Player has no motion input)
  • Auto Configuration: No visu password per default for mode switches

Audio

  • BG-I19330 Audio Player: don’t use decimal places for volume parameters
  • BG-I18904 Music Player: Input P always on when triggered via Player Group
  • BG-I18254 Central Audio: Send Alarm,Bell for Music Server as group events
  • BG-I14743 Central Audio: grouped bell off is sent if control is located on client
  • BG-I17237 Central Audio: grouped event is also sent to music servers
  • BG-I18965 Updating Audioserver-IP does not refresh configured-state of audio players
  • BG-I18827 Audioserver system messages displayed twice in client gateway systems
  • Stereo Extension: Room not displayed in periphery tree
  • BG-I19648 Line In ID displayed on Miniserver Compact
  • BG-I19330 Music Player: do not allow negative values for parameter BuzzerFav
  • Added volume state to audio player
  • Music Player: play because of presence not sent after reboot of miniserver+audioserver
  • BG-I21253: Audio Central: commands for Music server not executed
  • BG-I21442 Audio Central: Block ignores selected music server zones
  • BG-I21414 Music Server Zone: shown as offline in Device Status
  • BG-T2892 MS Compact: Internal Audioserver was not notified of planned reboot

Automatic Designer

  • BG-I18912 Automatic designer: Operating modes not shown when defined
  • BG-I18990 Automatic designer: Date-edit text cut off
  • BG-I17361 Automatic designer: rules with conditions using “not equal” are executing after change via app
  • BG-I19009 Automatic Scene: actions after wait conditions are not executed
  • Automatic rule: Edit dialog entries have missing text
  • Added Wallbox to Automatikdesigner
  • BG-I20843: Automatic designer: invalid maximum number of musicserver-zone-favourites
  • BG-I21448 Automatic Designer Dialog: fixed crash when filtering empty list
  • BG-I20823 Automatic Designer: Added Meter objects
  • BG-I19121 Automatic Designer Dialog: Controls with no actions/conditions are shown
  • BG-I18164 Automatic Rule: liveview not updated for new rules
  • Automatic Designer Dialog: rooms without valid controls are shown in room/category list
  • BG-I22289 Automatic Designer Dialog: config crash when using network intercommunication

Project Planning

  • Wallbox missing in project planning
  • BG-I19957 Project Planning: Multi Extension causes a second power supply &amp; backup
  • BG-I20265 Fixed output in power usage sheet (project planning)
  • BG-I19693 Fixed addition of devices in project planning
  • BG-I20538 Project Planning: Invalid power used for Valve Tree
  • Project Planning: Moved weatherstation to outside in DEU Default file
  • BG-I21351 Project Planning: Nanos get an unwanted topmodule
  • BG-I13784 Project Planning: PWM products are combined to one dimmer even when having a different name (only installation place was used to differentiate)
  • BG-I21627 Project Planning: Invalid power calculation for relay extension
  • BG-I22583 Project Planning: Dropdown overlaps checkbox
  • BG-I22590 Project Planning: Negative surcharge

Device Status

  • BG-I19574 US/IL channels not checked on all AirBase-Types
  • BG-I18619 Add spinner-animation for longer requests (deviceinfo, logfile,…)
  • BG-I20115 Get Log File Command not working when Miniserver is configured with custom Port
  • BG-I20864 No device type for Extensions
  • BG-I20013 Updated device-info-capabilities for 1Wire, RS232, RS485
  • BG-I20824 Remove sleep/wakeup commands for non-battery-devices
  • BG-I20710 Miniserver reboot via device status, reconnect after reboot

Device Learning

  • Device Learning: Data is not committed when device is replaced where setting is currently edited
  • Device Learning: Invalid filter set when starting search via context menu
  • Tree device learning: Device type column too small
  • BG-I20908 Air Learning: Device not found again after unpairing directly after learning it
  • BG-I21290 Device Learning: Identify not stopped when item is unselected

Dali Learning:

  • Conflicts are now resolved automatically
  • Searching for a lot of devices locks up config
  • Removed visual confirmation and load factory defaults for simplicity
  • Added buttons to turn on/off all lights
  • Search not aborted when stopping search or closing dialog
  • Address duplication is shown when manually editing address
  • Extensions not sorted
  • App Learning: Tree search results disappear
  • BG-I21056 App Air search on gateway not working properly
  • BG-I21749 Internorm device search results were missing correct serial number assignments

Sequence Controller

  • BG-I20529 Creates an if statement when it should not be needed
  • BG-I20386 Spaces added in between variable for TQ
  • BG-I17511 Set TQ Command Copying Text from Texteditor results in red line
  • BG-I18156 Does not correctly work with formula without space
  • BG-I18198 Invalid cursor position after auto-format
  • BG-I20780 goto-commands not adapted for undo or every line break
  • BG-I20838 Comments are shown as error in text editor
  • Goto-update not working with uppercases
  • BG-I21642 Crash when cancelling sequence renaming
  • BG-I21720 Text-output not trimmed

Stability

  • BG-I19414 Config crash when renaming Wallbox Gen.1 after cut/paste
  • BG-I19223 Config crash when saving to Miniserver
  • BG-I19278 Config crash when starting simulation
  • BG-I19359 Config crash in Media object dialog
  • BG-I19206 Config crash when deleting Power Supply &amp; Backup
  • BG-I19192 Config crash when editing settings
  • BG-I19862 Config Crash Right Click Valve Actor while Virtual Input is selected
  • BG-I19279 Config crash when editing setting and then clicking a button
  • BG-I18983 Loxone Config freezes when using hostnames in a gateway project
  • BG-I18434 Config crash during auto configuration
  • BG-I20085 Config crash after paste
  • Multiplicator: Config crash when loading from Miniserver
  • Multiplicator: Config crash when loading from Miniserver
  • Config crash due to high communication traffic in big installations
  • Config crash while learning devices
  • BG-I19812 Config can not be closed
  • Miniserver reboot when tcp socket is deleted after incomplete tcp handshake
  • BG-I20547 Miniserver reboot when setting user attribute to empty from app
  • BG-I20797 Miniserver reboot when saving to large Client/Gateway installations
  • BG-I20886 Config crash when changing topmodule
  • Config crash when starting Miniserver search
  • BG-I20849 Lighting Controller: Config crash when deleting moods in dialog
  • Miniserver not restarting after crash
  • BG-I20850 Config crash when deleting project from overview
  • Gateway rebooting in rare cases when saving to Miniserver
  • Config crash when starting link search a second time
  • Config Crash when sending large encrypted webservice
  • BG-I19806 Config crash when opening project from project view
  • BG-I21417 Config crash when creating new projects
  • BG-I21400 Config crash when creating connection flags
  • BG-I21642 Sequence Controller: Crash when cancelling sequence renaming
  • BG-I21482 Config crash when opening config
  • BG-I21632 Config crash when deleting control
  • BG-I21630 Config crash when receiving invalid search answer
  • BG-I21804 Config crash when managing SD card
  • Fixed Debug Monitor causing ddos and memory leak on Miniserver Gen.1 by sending data to itself
  • Improved handling of a lot of HTTP requests
  • BG-I20901 possible crash when adding Enocean device via learning dialog
  • BG-I21948 Config crash when editing user rights
  • BG-I20678 High memory usage on Miniserver Gen.1 due to FTP file download resulting in possible out of memory crashes
  • BG-I21679 Miniserer crash with broken file
  • BG-I22086 Config crash when device update is reported
  • BG-I22180 Miniserver reboot with invalid 1-wire devices on a Multi Extension
  • BG-I22038 Config cant be closed after opening project planning file
  • BG-I22344 Config crash when opening Monitor
  • BG-I22506 Config crash when creating file for a gateway Miniserver
  • Config crash when formatting a second SD without closing dialog
  • BG-I22366 Config crash when editing in multi edit view
  • BG-I22446 Config crash after deleting device reference
  • BG-I22581 Config crash after insert of energy flow monitor
  • BG-I22480 Config crash when saving Monitor as csv
  • BG-I21647 Communications failure
  • BG-I22677 Config crash when loading from Miniserver</v1>