Update

Enhanced Redundancy Bundle Update for Connectivity Modules

New Features:

Nothing known

Enhancements:

  • The 1756-CN2, 1756-CN2R, 1756-CN2RXT, and 1756-CN2RK modules are available with firmware revision 25.005.
  • 1756-EN2F/C modules now have firmware revision 10.009 in the enhanced redundancy bundle.
  • 1756-CN2/C support with firmware revision 20.055_kit4 is included.
  • The 1756-RM2 and 1756-RM2XT modules utilize firmware revision 20.005.
  • The Redundancy Module Configuration Tool (RMCT) has been updated to version 8.02.01.

Fixed Bugs:

  • Resolved issue: Cycle Power to Unit no longer asserts in CnetSchedTransmitList.cpp Line 258 for channel faults (Late clock lock). Rack-optimized outputs now transition correctly.

Open Issues:

  • Multiple switchovers can cause connection failure to SoftLogix controllers.
  • Connections may drop temporarily if a 1756-EN2Tx communication module is not configured correctly.
  • Redundant chassis synchronization fails when the controller nears its connection limit.
  • Alarms scanned during the continuous task can be published to the alarm server twice after a switchover.
  • Alarm status messages may be duplicated in the Alarm History Log after a switchover.

Update Instructions:

Nothing known

The manufacturer Rockwell Automation has not yet set up its devicebase profile. Content such as updates, compatibilities and support may only be maintained with a delay.
Receive Important Update Messages Stay tuned for upcoming Rockwell Automation updates

Was the content helpful to you?

Advertisement Advertise here?
Udemy IT certification ad