Siemens Releases Update for SIMATIC ET 200SPTM ECC 2xPWM ST
New Features:
- Emergency release: New option allows the customer to repeat unlatching of defective latch.
 - Control of ACT interlock outputs: Users can now control interlock outputs directly from PIQ3 with new PIQ bits.
 - Bit 5: 0: Both ACT outputs are high impedance; driven to 0V or 12V based on bits 6 and 7.
 - Bit 6: For Bit 5 = 1: 0: Output ACT + = 0V; 1: Output ACT + = 12V.
 - Bit 7: For Bit 5 = 1: 0: Output ACT– = 0V; 1: Output ACT– = 12V.
 
Enhancements:
Nothing known
Fixed Bugs:
Nothing known
Open Issues:
Nothing known
Update Instructions:
- A previous software version is required for this update.
 