User Experience Improvement with Firmware V4.1.4
Update V4.1.4 for 6ES7517-4HQ10-0AB0 and 6ES7518-4JT10-0AB0
User Experience Improvement with Firmware V4.1.4 for S7-1500 H/HF CPUs:
The following error has been fixed:
- After adding an IO device with System redundancy R1 in the operating state RUN-Redundant, the subsequent deletion of the IO device in the operating state STOP and adding it again, the redundant system S7-1500 H/HF go into the "defective" state. This behavior has been fixed.
- After adding and charging a CiR-enabled IO device in the operating state RUN-redundant and a subsequent SYNCUP, the Connection to this IO device may not be uninterrupted can be carried out. This behavior has been fixed.