Updates for block library SIMOCODE pro for SIMATIC PCS 7 Version V9
Siemens has released updates for the SIMOCODE pro block library on 09/29/2020. These updates bring novelties and improvements over previous versions. The news is:
- MMRevDhl-The Feature2.Bit9 is introduced to enable the "Button mode in Local mode" function. A control in local mode is only possible with a 0 -> 1 edge of the command signal
- MMDiag, MMOprtn, MMMeas, MMStat, and MMLog– CPU work memory may get loaded during system function calls SFB52 "RDREC", SFB53 "WRREC" and SFC13 "DPNRM_DG" from multiple blocks, this behavior has now been enhanced in such a way that MMDiag, MMOprtn, MMMeas, MMStat, and MMLog blocks will automatically clear the CPU buffer memory if it is occupied by incomplete calls of SFB52 "RDREC", SFB53 "WRREC" and SFC13 "DPNRM_DG".
- The last valid states of the blocks are retained during HCiR (Download station configuration in RUN mode).
There are also a lot of bugs fixed in this update.