New Fail-safe analog input module with HART communication
The new fail-safe product can expand the high-performance SIMATIC ET 200SP HA I/O for the process industry, meaning that is possible for the majority of the fail-safe function to be controlled with the SIMATIC ET 200SP HA I/O based on SIMATIC Safety Integrated for Process Automation.
Product information
Technical product information and properties:
- 8 fail-safe analog inputs
- Measuring ranges: 0..20 mA and 4..20 mA
- Resolution: 16 bits including sign
- Short-circuit proof internal encoder supply for two-wire measuring transducer
- External encoder supply possible
- Programmable diagnostics
- Channel-wide and module-wide passivation
- HART communication (Rev. 5 to Rev. 7)
- PROFIsafe profile V2.6.1
Product supported functions:
- Firmware update
- Identification data I&M
- Value status
- IO redundancy
Important notes and requirements
Required software for configuration of the fail-safe I/O module:
- S7 F Systems V6.4 (or higher)
- PCS 7 V9.1 + HUP (or higher) or PCS 7 V9.0 SP3 + HUP (or higher)
Or, the following:
- S7 F Systems V6.4 (or higher)
- STEP 7 from V5.6 SP2 and CFC from V9.0 SP4